SHORT CIRCUIT TESTING
For a range of cleats to be classified under the Standard at a particular fault level, it must undergo one or two short circuit tests depending on classification and afterwards:
- There shall be no failure that will affect the intended function of holding the cable in place.
- The cable cleats and intermediate restraints, if used, shall be intact with no missing parts (minor deformation is acceptable).
- There shall be no cuts or damage visible to the outer sheath of the cable caused by the cleats or intermediate restraints.
- There shall be no failure that will affect the intended function of holding the cable in place.
- The cable cleats and intermediate restraints, if used, shall be intact with no missing parts (minor deformation is acceptable).
- There shall be no cuts or damage visible to the outer sheath of the cable caused by the cleats or intermediate restraints.